Danfoss VLT AutomationDrive FC 301 Programming Manual page 608

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT AutomationDrive FC 301/302
Programming Guide
Option
[0]*
[1]
Parameter 33-44 Positive Software End Limit Active
Table 1201: Parameter 33-44 Positive Software End Limit Active
33-44 Positive Software End Limit Active
Default value: [0] Inactive
Conversion index: -
When this parameter is set to active, the drive continuously checks whether the target position is above the positive software limit.
If the position is outside the limit, an error is issued and the drive control is switched off.
Option
[0]*
[1]
Parameter 33-45 Time in Target Window
Table 1202: Parameter 33-45 Time in Target Window
33-45 Time in Target Window
Default value: 0
Conversion index: -3
Parameter 33-46 Target Window LimitValue
Table 1203: Parameter 33-46 Target Window LimitValue
33-46 Target Window LimitValue
Default value: 1
Conversion index: 0
Parameter 33-47 Size of Target Window
Table 1204: Parameter 33-47 Size of Target Window
33-47 Size of Target Window
Default value: 0
Conversion index: 0
Defines the size of the target window with user unit. A position is only viewed as reached when the actual position is within this
window.
608 | Danfoss A/S © 2022.12
Name
Inactive
Active
Parameter type: Option
Data type: Uint8
Name
Inactive
Active
Parameter type: Range, 0 - 10 ms
Data type: Uint8
Parameter type: Range, 1 - 10000 ms
Data type: Uint16
Parameter type: Range, 0 - 10000 ms
Data type: Uint16
Parameter Descriptions
Description
Setup: 2 setups
Change during operation: True
Description
Setup: 2 setups
Change during operation: True
Setup: 2 setups
Change during operation: True
Setup: 2 setups
Change during operation: True