VLT AutomationDrive FC 301/302
Programming Guide
Option
[90]
kWh counter pulse
[90]
kWh counter pulse
[98]
Virtual master dir.
[120]
Local ref active
Table 354: Local Reference Active
Reference site set in parameter 3-13 Reference Site
Reference site: Local parameter 3-13 Reference Site [2] Local
Reference site: Remote parameter 3-13 Reference Site [1] Remote
Reference site: Linked to Hand/ Auto
Hand
Hand⇒off
Auto⇒off
Auto
Table 355: 5-30 Digital Outputs - 2
Option
[121]
Remote ref active
[122]
No alarm
[123]
Start command ac-
tive
[124]
Running reverse
[125]
Drive in hand mode
[126]
Drive in auto mode
[151]
ATEX ETR cur. alarm
202 | Danfoss A/S © 2022.12
Function
Sends a pulse (200 ms pulse width) to output terminal whenever kWh counter changes (parameter
15-02 kWh Counter).
This option is only available with software version 48.XX.
Sends a pulse (200 ms pulse width) to the output terminal whenever kWh counter changes (pa-
rameter 15-02 kWh Counter).
This option is only available with software version 48.XX.
A virtual master signal that controls the rotation direction of followers.
Output is high when parameter 313 Reference Site = [2] Local.
Function
Output is high when parameter 3-13 Reference Site = [1] Remote or [0] Linked to hand/auto while
the LCP is in auto-on mode. See
Output is high when no alarm is present.
Output is high when there is an active start command (that is via digital input bus connection,
hand-on, or auto-on), and no stop or start command is active.
Output is high when the drive runs counterclockwise (the logical product of the status bits run-
ning AND reverse).
Output is high when the drive is in hand-on mode (as indicated by the LED light above [Hand
On]).
Output is high when the drive is in auto-on mode (as indicated by the LED light above [Auto On]).
Selectable if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR. If
Alarm 164 ATEX ETR cur.lim.alarm is active, the output is 1.
N O T I C E
N O T I C E
Local reference active [120]
1
0
1
1
0
0
Table
354.
Parameter Descriptions
Remote reference active [121]
0
1
0
0
0
1
AU275636650261en-000101 / 130R0334