VLT AutomationDrive FC 301/302
Programming Guide
Parameter 17-42 Fieldbus Velocity FF.
Table 926: Parameter 17-42 Fieldbus Velocity FF.
17-42 Fieldbus Velocity FF.
Default value: 0
Parameter type: Range, -2147483648 - 2147483647 pu/s
Conversion index: 0
Data type: Int32
This parameter is only available with software version 48.XX.
Velocity feedforward when running in cyclic sync. position mode.
Parameter 17-43 Fieldbus Acceleration FF.
Table 927: Parameter 17-43 Fieldbus Acceleration FF.
17-43 Fieldbus Acceleration FF.
Default value: 0
Parameter type: Range, -2147483648 - 2147483647 pu/s
Conversion index: 0
Data type: Int32
This parameter is only available with software version 48.XX.
Acceleration feedforward when running cyclic sync. position or cyclic sync. velocity mode.
Parameter 17-44 Fieldbus Target Velocity
Table 928: Parameter 17-44 Fieldbus Target Velocity
17-44 Fieldbus Target Velocity
Default value: 0
Parameter type: Range, -2147483648 - 2147483647 pu/s
Conversion index: 0
Data type: Int32
This parameter is only available with software version 48.XX.
Velocity reference when running cyclic sync. velocity mode.
5.17.5 17-5* Resolver Interface
This parameter group is used for setting parameters for the VLT® Resolver Input MCB 103. Usually, the resolver feedback is used as
motor feedback from permanent magnet motors with parameter 1-01 Motor Control Principle set to [3] Flux w/motor feedback. Re-
solver parameters cannot be adjusted while the motor is running.
Parameter 17-50 Poles
Table 929: Parameter 17-50 Poles
17-50 Poles
Default value: 2
Conversion index: 0
Set the pole number on the resolver. The value is stated in the datasheet for resolvers.
Danfoss A/S © 2022.12
N O T I C E
N O T I C E
N O T I C E
Parameter type: Range, 2 - 8
Data type: Uint8
Parameter Descriptions
Setup: 1 setup
Change during operation: True
2
Setup: 1 setup
Change during operation: True
Setup: 1 setup
Change during operation: True
Setup: 1 setup
Change during operation: False
AU275636650261en-000101 / 130R0334 | 521