Danfoss VLT AutomationDrive FC 301 Programming Manual page 391

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT AutomationDrive FC 301/302
Programming Guide
Option
Name
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[39]
Start command
[40]
Drive stopped
[41]
Reset trip
[42]
Auto-reset trip
[43]
OK key
[44]
Reset key
[45]
Left key
[46]
Right key
[47]
Up key
[48]
Down key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL time-out 3
[71]
SL time-out 4
[72]
SL time-out 5
[73]
SL time-out 6
[74]
SL time-out 7
[75]
Start command given
[76]
Digital input X30/2
[77]
Digital input X30/3
[78]
Digital input X30/4
[79]
Digital input 46/1
[80]
Digital input 46/3
[81]
Digital input 46/5
[82]
Digital input 46/7
Danfoss A/S © 2022.12
Description
This option is only available in FC 302.
[OK] is pressed. Only available on the graphical LCP.
[Reset] is pressed. Only available on the graphical LCP.
[◃] is pressed. Only available on the graphical LCP.
[▹] is pressed. Only available on the graphical LCP.
[▵] is pressed. Only available on the graphical LCP.
[▿] is pressed. Only available on the graphical LCP.
N O T I C E
AU275636650261en-000101 / 130R0334 | 391
Parameter Descriptions