VLT AutomationDrive FC 301/302
Programming Guide
Set the maximum frequency for terminal 29 corresponding to the output variable selected in parameter 5-63 Terminal 29 Pulse Out-
put Variable.
Parameter 5-66 Terminal X30/6 Pulse Output Variable
Table 379: Parameter 5-66 Terminal X30/6 Pulse Output Variable
5-66 Terminal X30/6 Pulse Output Variable
Default value: Size related
Conversion index: –
Select the variable for readout on terminal X30/6. This parameter is active when VLT® General Purpose I/O MCB 101 is installed in the
drive. The options and functions are the same as in parameter group 5-6* Pulse Outputs.
Option
Name
[0]
No operation
[45]
Bus ctrl.
[48]
Bus ctrl., timeout
[51]
MCO controlled
[97]
Reference after ramp
[99]
Virtual master speed
[100]
Output frequency
[101]
Reference
[102]
Feedback
[103]
Motor current
[104]
Torque rel to limit
[105]
Torque related to rated
[106]
Power
[107]
Speed
[108]
Torque
[109]
Max out freq
[119]
Torque % lim
224 | Danfoss A/S © 2022.12
Parameter type: Option
Data type: Uint8
Description
Select the display output for terminal 27.
This option is only available with software version 48.XX.
Actual speed reference after the ramp. Use this output as master signal for speed synchroni-
zation of follower drives. The reference is set in parameter 16-48 Speed Ref. After Ramp [RPM].
This option is only available with software version 48.XX.
Virtual master signal for controlling the speed or position of the followers.
Setup: All setups
Change during operation: True
N O T I C E
N O T I C E
AU275636650261en-000101 / 130R0334
Parameter Descriptions