VLT AutomationDrive FC 301/302
Programming Guide
Parameter 15-20 Historic Log: Event
Table 778: Parameter 15-20 Historic Log: Event
15-20 Historic Log: Event
Default value: 0
Conversion index: 0
View the event type of the logged events.
Parameter 15-21 Historic Log: Value
Table 779: Parameter 15-21 Historic Log: Value
15-21 Historic Log: Value
Default value: 0
Conversion index: 0
View the value of the logged event. Interpret the event values as below:
Digital input
Digital output (not
monitored in this SW re-
lease)
Warning word
Alarm word
Status word
Control word
Extended status word
Parameter 15-22 Historic Log: Time
Table 780: Parameter 15-22 Historic log: Time
15-22 Historic log: Time
Default value: 0 ms
Parameter type: Range, 0 - 2147483647 ms, Array [50]
Conversion index: -3
Data type: Uint32
View the time at which the logged event occurred. Time is measured in ms since the drive was started. The maximum value corre-
sponds to approximately 24 days, which means that the count restarts at 0 after this period.
5.15.9 15-3* Alarm Log
Parameters in this group are array parameters where up to 10 fault logs can be viewed. 0 is the most recent logged data and 9 is the
oldest. Fault codes, values, and time stamp can be viewed for all logged data.
Parameter 15-30 Fault Log: Error Code
Table 781: Parameter 15-30 Fault Log: Error Code
15-30 Fault Log: Error Code
Default value: 0
Conversion index: 0
488 | Danfoss A/S © 2022.12
Parameter type: Range, 0 - 255, Array [50]
Data type: Uint8
Parameter type: Range, 0 - 2147483647, Array [50]
Data type: Uint32
Decimal value. See parameter 16-60 Digital Input for a description after converting to binary value.
Decimal value. See parameter 16-66 Digital Output [bin] for a description after converting to binary val-
ue.
Decimal value. See parameter 16-92 Warning Word for a description.
Decimal value. See parameter 16-90 Alarm Word for a description.
Decimal value. See parameter 16-03 Status Word for a description after converting to binary value.
Decimal value. See parameter 16-00 Control Word for a description.
Decimal value. See parameter 16-94 Ext. Status Word for a description.
Parameter type: Range, 0 - 65535, Array [10]
Data type: Uint16
Parameter Descriptions
Setup: All setups
Change during operation: False
Setup: All setups
Change during operation: False
Setup: All setups
Change during operation: False
Setup: All setups
Change during operation: False