Programming Guide
Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
X48/10. A high time constant value improves dampening but also increases the time delay through the filter.
Parameter 35-35 Term. X48/10 Temp. Monitor
Table 1295: Parameter 35-35 Term. X48/10 Temp. Monitor
35-35 Term. X48/10 Temp. Monitor
Default value: [0] Disabled
Conversion index: -
This parameter facilitates the possibility of enabling or disabling the temperature monitor for terminal X48/4. Set the temperature
limits in parameter 35-36 Term. X48/10 Low Temp. Limit and parameter 35-37 Term. X48/10 High Temp. Limit.
Option
[0]*
[1]
Parameter 35-36 Term. X48/10 Low Temp. Limit
Table 1296: Parameter 35-36 Term. X48/10 Low Temp. Limit
35-36 Term. X48/10 Low Temp. Limit
Default value: Size related
Conversion index: 0
Enter the minimum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/10.
Parameter 35-37 Term. X48/10 High Temp. Limit
Table 1297: Parameter 35-37 Term. X48/10 High Temp. Limit
35-37 Term. X48/10 High Temp. Limit
Default value: Size related
Conversion index: 0
Enter the maximum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/10.
5.28.5 35-4* Analog Input X48/2
Parameter 35-42 Term. X48/2 Low Current
Table 1298: Parameter 35-42 Term. X48/2 Low Current
35-42 Term. X48/2 Low Current
Default value: 4 mA
Conversion index: -3
Enter the current (mA) that corresponds to the low reference value set in parameter 35-44 Term. X48/2 Low Ref./Feedb. Value. The
value must be more than 2 mA to activate the live zero timeout function in parameter 6-01 Live Zero Timeout Function.
Parameter 35-43 Term. X48/2 High Current
Table 1299: Parameter 35-43 Term. X48/2 High Current
35-43 Term. X48/2 High Current
Default value: 20 mA
Conversion index: -3
Danfoss A/S © 2022.12
Parameter type: Option
Data type: Uint8
Name
Disabled
Enabled
Parameter type: Range, N/A
Data type: Int16
Parameter type: Range, N/A
Data type: Int16
Parameter type: Range, 0 - 20 mA
Data type: Int16
Parameter type: Range, 0 - 20 mA
Data type: Int16
Parameter Descriptions
Setup: All setups
Change during operation: True
Description
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334 | 635