Parameter 23-12 Maintenance Base
Table 1030: Parameter 23-12 Maintenance Base
23-12 Maintenance Base
Default value: Size related
Conversion index: -
Select the time base to be associated with the preventive maintenance event.
Option
Name
[0]
Disabled
[1]
Running hours
[2]
Operating hours
[3]
Date & time
[4]
No of counts
Parameter 23-13 Maintenance Interval
Table 1031: Parameter 23-13 Maintenance Interval
23-13 Maintenance Interval
Default value: 1
Conversion index: 0
Set the interval associated with the current preventive maintenance event. This parameter is only used if [1] Running Hours or [2]
Operating Hours is selected in parameter 23-12 Maintenance Base. The timer is reset in parameter 23-15 Reset Maintenance Word.
Example
A preventive maintenance event is set up Monday at 8:00. Parameter 23-12 Maintenance Base is [2] Operating hours and parameter
23-13 Maintenance Interval is 7 x 24 hours=168 hours. Next maintenance event is indicated the following Monday at 8:00. If this
maintenance event is not reset until Tuesday at 9:00, the next occurrence is the following Tuesday at 9:00.
Parameter 23-14 Maintenance Data and Time
Table 1032: Parameter 23-14 Maintenance Data and Time
23-14 Maintenance Data and Time
Default value: Size related
Conversion index: 0
Set the date and time for the next maintenance occurrence if the preventive maintenance event is based on date/time. Date format
depends on the setting in parameter 0-71 Date Format while the time format depends on the setting in parameter 0-72 Time Format.
560 | Danfoss A/S © 2022.12
Name
Maintenance text 4
Maintenance text 5
Clear logs
Parameter type: Option, Array [6]
Data type: Uint8
Description
Disables the preventive maintenance event.
The number of hours the motor has run. Running hours are not reset at power-on. Specify the main-
tenance time interval in parameter 23-13 Maintenance Interval.
The number of hours the drive has run. Operating hours are not reset at power-on. Specify the
maintenance time interval in parameter 23-13 Maintenance Interval.
Uses the internal clock. Specify the date and time of the next maintenance occurrence in parameter
23-14 Maintenance Date and Time.
Parameter type: Range, 1 - 2147483647, Array [6]
Data type: Uint32
Parameter type: Range, 0 - 0, Array [6]
Data type: TimeOfDay
Parameter Descriptions
Description
Setup: 1 setup
Change during operation: True
Setup: 1 setup
Change during operation: True
Setup: 1 setup
Change during operation: True