VLT AutomationDrive FC 301/302
Programming Guide
5.28.3 35-2* Temp. Input X48/7
Table 1290: Parameter 35-24 Term. X48/7 Filter Time Constant
35-24 Term. X48/7 Filter Time Constant
Default value: 0.001 s
Conversion index: 0
Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal
X48/7. A high time constant value improves dampening but also increases the time delay through the filter.
Parameter 35-25 Term. X48/7 Temp. Monitor
Table 1291: Parameter 35-25 Term. X48/7 Temp. Monitor
35-25 Term. X48/7 Temp. Monitor
Default value: [0] Disabled
Conversion index: -
This parameter facilitates the possibility of enabling or disabling the temperature monitor for terminal X48/4. Set the temperature
limits in parameter 35-26 Term. X48/7 Low Temp. Limit and parameter 35-27 Term. X48/7 High Temp. Limit.
Option
[0]*
[1]
Parameter 35-26 Term. X48/7 Low Temp. Limit
Table 1292: Parameter 35-26 Term. X48/7 Low Temp. Limit
35-26 Term. X48/7 Low Temp. Limit
Default value: Size related
Conversion index: 0
Enter the minimum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/7.
Parameter 35-27 Term. X48/7 High Temp. Limit
Table 1293: Parameter 35-27 Term. X48/7 High Temp. Limit
35-27 Term. X48/7 High Temp. Limit
Default value: Size related
Conversion index: 0
Enter the maximum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/7.
5.28.4 35-3* Temp. Input X48/10
Parameter 35-34 Term. X48/10 Filter Time Constant
Table 1294: Parameter 35-34 Term. X48/10 Filter Time Constant
35-34 Term. X48/10 Filter Time Constant
Default value: 0.001 s
Conversion index: 0
634 | Danfoss A/S © 2022.12
Parameter type: Range, 0.001 - 10 s
Data type: Uint16
Parameter type: Option
Data type: Uint8
Name
Disabled
Enabled
Parameter type: Range, N/A
Data type: Int16
Parameter type: Range, N/A
Data type: Int16
Parameter type: Range, 0.001 - 10 s
Data type: Uint16
Parameter Descriptions
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Description
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334