VLT AutomationDrive FC 301/302
Programming Guide
7.2.38 WARNING 40, Overload of Digital Output Terminal 27
Troubleshooting
Check the load connected to terminal 27 or remove the short-circuit connection.
Check parameter 5-00 Digital I/O Mode and parameter 5-01 Terminal 27 Mode.
7.2.39 WARNING 41, Overload of Digital Output Terminal 29
Troubleshooting
Check the load connected to terminal 29 or remove the short-circuit connection.
Check parameter 5-00 Digital I/O Mode and parameter 5-02 Terminal 29 Mode.
7.2.40 WARNING 42, Ovrld X30/6-7
Troubleshooting
For terminal X30/6:
Check the load connected to the terminal, or remove the short-circuit connection.
Check parameter 5-32 Term X30/6 Digi out (MCB 101) (VLT® General Purpose I/O MCB 101).
For terminal X30/7:
Check the load connected to the terminal, or remove the short-circuit connection.
Check parameter 5-33 Term X30/7 Digi Out (MCB 101) (VLT® General Purpose I/O MCB 101).
7.2.41 ALARM 43, Ext. Supply
Cause
VLT® Extended Relay Option MCB 113 is mounted without 24 V DC.
Troubleshooting
Choose 1 of the following:
Connect a 24 V DC external supply.
Specify that no external supply is used via parameter 14-80 Option Supplied by External 24VDC, [0] No. A change in parameter
14-80 Option Supplied by External 24VDC requires a power cycle.
7.2.42 ALARM 45, Earth Fault 2
Cause
Ground fault.
Troubleshooting
Check for proper grounding and loose connections.
Check for proper wire size.
Check the motor cables for short circuits or leakage currents.
7.2.43 ALARM 46, Power Card Supply
Cause
The supply on the power card is out of range. Another reason can be a defective heat sink fan.
There are 3 supplies generated by the switch mode supply (SMPS) on the power card:
24 V.
5 V.
±18 V.
When powered with VLT
24 V DC Supply MCB 107, only 24 V and 5 V supplies are monitored. When powered with 3-phase mains
®
voltage, all 3 supplies are monitored.
Troubleshooting
Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
708 | Danfoss A/S © 2022.12
Troubleshooting
AU275636650261en-000101 / 130R0334