Load Depend. Setting - Danfoss VLT AutomationDrive FC 301 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT AutomationDrive FC 301/302
Programming Guide
Parameter 1-59 Flying Start Test Pulses Frequency
Table 110: Parameter 1-59 Flying Start Test Pulses Frequency
1-59 Flying Start Test Pulses Frequency
Default value: Size related
Conversion index: 0
Asynchronous motor: Set the frequency of the flying start test pulses that are used to detect the motor direction. For asynchronous
motors, the value 100% means that the slip is doubled. Increase this value to reduce the generated torque. For synchronous motors,
this value is the percentage n
start mode is selected in parameter 1-70 Start Mode.

5.2.7 1-6* Load Depend. Setting

The following parameters are only available in FC 302:
-
Parameter 1-66 Min. Current at Low Speed
-
Parameter 1-67 Load Type
-
Parameter 1-68 Motor Inertia
-
Parameter 1-69 System Inertia
Parameter 1-60 Low Speed Load Compensation
Table 111: Parameter 1-60 Low Speed Load Compensation
1-60 Low Speed Load Compensation
Default value: 100%
Conversion index: 0
Enter the % value to compensate voltage in relation to load when the motor is running at low speed and obtain the optimum U/f
characteristic. The motor size determines the frequency range within which this parameter is active.
Motor size
0.25–7.5 kW
11–45 kW
55–maximum power size kW
92 | Danfoss A/S © 2022.12
Parameter type: Range, 0 - 500%
Data type: Uint16
of the free-running motor. Above this value, flying start is always performed. Below this value, the
m,n
N O T I C E
Parameter type: Range, 0 - 300%
Data type: Int16
Parameter Descriptions
Setup: All setups
Change during operation: False
Setup: All setups
Change during operation: True
Changeover
<10 Hz
<5 Hz
<3–4 Hz
AU275636650261en-000101 / 130R0334

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents