Danfoss VLT AutomationDrive FC 301 Programming Manual page 112

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT AutomationDrive FC 301/302
Programming Guide
Application
I
/I
> 50
Load
Motor
High load at low speed <30% (rated
speed)
If the motor starts oscillating at a certain speed, increase parameter 1-14 Damping Gain. Increase the value in small steps. Depending
on the motor, a good value for this parameter can be 10% or 100% higher than the default value.
Adjust starting torque in parameter 1-66 Min. Current at Low Speed. 100% provides nominal torque as starting torque.
Table 149: Recommendations for Flux Applications
Application
Low inertia applications
High inertia applications
High load at low speed
Adjust starting torque in parameter 1-66 Min. Current at Low Speed. 100% provides nominal torque as starting torque.
5.3 Parameter Group 2-** Brakes
5.3.1 2-0* DC Brakes
Parameter group for configuring the DC brake and DC hold functions.
Parameter 2-00 DC Hold Current
Table 150: Parameter 2-00 DC Hold Current
2-00 DC Hold Current
Default value: 50%
Conversion index: 0
The maximum value depends on the rated motor current. Avoid 100% current for too long. It may damage the motor. In VVC+
control core, low values (<20%) of DC hold may result in wrong currents with larger motor sizes (>90 kW) and should be avoided.
In cases when low DC hold currents with larger motors are required, select Flux control core to ensure the right currents.
Enter a value for holding current as a percentage of the rated motor current I
current corresponds to I
. This parameter holds the motor function (holding torque) or preheats the motor. This parameter is ac-
M,N
tive if DC hold is selected in parameter 1-72 Start Function [0] or parameter 1-80 Function at Stop [1].
Parameter 2-01 DC Brake Current
Table 151: Parameter 2-01 DC Brake Current
2-01 DC Brake Current
Default value: 50%
Conversion index: 0
The maximum value depends on the rated motor current. Avoid 100% current for too long. It may damage the motor.
112 | Danfoss A/S © 2022.12
Settings
Increase parameter 1-17 Voltage filter time const. Increase parameter 1-66 Min. Current
at Low Speed (>100% for longer time can overheat the motor).
Settings
Keep calculated values.
Parameter 1-66 Min. Current at Low Speed. Increase speed to a value between default and maximum
depending on application. Set ramp times matching the application. Too fast ramp-up causes an
overcurrent/overtorque. Too fast ramp-down causes an overvoltage trip.
Parameter 1-66 Min. Current at Low Speed. Increase speed to a value between default and maximum
depending on application.
Parameter type: Range, 0 - 160%
Data type: Uint8
N O T I C E
Parameter type: Range, 0 - 1000%
Data type: Uint16
N O T I C E
Parameter Descriptions
Setup: All setups
Change during operation: True
set in parameter 1-24 Motor Current. 100% DC hold
M,N
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt automationdrive fc 302

Table of Contents