VLT AutomationDrive FC 301/302
Programming Guide
Parameter 6-14 Terminal 53 Low Ref./Feedb. Value
Table 404: Parameter 6-14 Terminal 53 Low Ref./Feedb. Value
6-14 Terminal 53 Low Ref./Feedb. Value
Default value: Size related
Conversion index: -3
Enter the analog input scaling value that corresponds to the low voltage/low current set in parameter 6-10 Terminal 53 Low Voltage
and parameter 6-12 Terminal 53 Low Current.
Parameter 6-15 Terminal 53 High Ref./Feedb. Value
Table 405: Parameter 6-15 Terminal 53 High Ref./Feedb. Value
6-15 Terminal 53 High Ref./Feedb. Value
Default value: Size related
Conversion index: -3
Enter the analog input scaling value that corresponds to the maximum reference feedback value set in parameter 6-11 Terminal 53
High Voltage and parameter 6-13 Terminal 53 High Current.
Parameter 6-16 Terminal 53 Filter Time Constant
Table 406: Parameter 6-16 Terminal 53 Filter Time Constant
6-16 Terminal 53 Filter Time Constant
Default value: 0.001 s
Conversion index: -3
This parameter cannot be adjusted while the motor is running.
Enter the filter time constant. This constant is a first-order digital low-pass filter time for suppressing electrical noise in terminal 53. A
high value improves dampening but also increases the delay through the filter.
5.7.3 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog input 2 (terminal 54).
Parameter 6-20 Terminal 54 Low Voltage
Table 407: Parameter 6-20 Terminal 54 Low Voltage
6-20 Terminal 54 Low Voltage
Default value: Size related
Conversion index: -2
Enter the low voltage value. This analog input scaling value should correspond to the minimum reference value set in parameter
3-02 Minimum Reference.
234 | Danfoss A/S © 2022.12
Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Data type: Int32
Parameter type: Range, -999999.999 - 999999.999 ReferenceFeed-
backUnit
Data type: Int32
Parameter type: Range, 0.001 - 10 s
Data type: Uint16
N O T I C E
Parameter type: Range, -10.00 - par. 6-21 V
Data type: Int16
Parameter Descriptions
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True
Setup: All setups
Change during operation: True