Danfoss VLT AutomationDrive FC 301 Programming Manual page 217

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

VLT AutomationDrive FC 301/302
Programming Guide
Selected
event
Relay
output
On delay
P 5-41
Selected
event
Relay
output
On delay
P 5-41
Illustration 63: On Delay, Relay
Parameter 5-42 Off Delay, Relay
Table 363: Parameter 5-42 Off Delay, Relay
5-42 Off Delay, Relay
Default value: 0.01 s
Conversion index: -2
Enter the delay of the relay cutout time. Select 1 of 2 internal mechanical relays in an array function. See parameter 5-40 Function
Relay for details. If the selected event condition changes before a delay timer expires, the relay output is unaffected.
Selected
event
Relay
output
On delay
P 5-41
Illustration 64: Off Delay, Relay
5.6.5 5-5* Pulse Input
The following parameters are only available in FC 302:
-
Parameter 5-50 Term. 29 Low Frequency
-
Parameter 5-51 Term. 29 High Frequency
-
Parameter 5-52 Term. 29 Low Ref./Feedb. Value
-
Parameter 5-53 Term. 29 High Ref./Feedb. Value
-
Parameter 5-54 Pulse Filter Time Constant #29
The pulse input parameters are used to define an appropriate window for the impulse reference area by configuring the scaling and
filter settings for the pulse inputs. Input terminals 29 or 33 act as frequency reference inputs. Set terminal 29 (parameter 5-13 Termi-
nal 29 Digital Input) or terminal 33 (parameter 5-15 Terminal 33 Digital Input) to [32] Pulse input. If terminal 29 is used as an input, set
parameter 5-01 Terminal 27 Mode to [0] Input.
Danfoss A/S © 2022.12
Off delay
P 5-42
Parameter type: Range, 0.01 – 600 s, Array [9]
Data type: Uint16
Off delay
P 5-42
N O T I C E
Parameter Descriptions
Setup: All setups
Change during operation: True
AU275636650261en-000101 / 130R0334 | 217