r2120

CO: Sum of fault and alarm buffer changes / Sum buffer changed

All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the sum of all of the fault and alarm buffer changes in the drive unit.
Dependency:
Refer to: r0944, r2121
r2121

CO: Counter alarm buffer changes / Alrm buff changed

All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
This counter is incremented every time the alarm buffer changes.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125
r2122[0...63]

Alarm code / Alarm code

All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
Displays the number of alarms that have occurred.
Dependency:
Refer to: r2110, r2123, r2124, r2125, r2134, r2145, r2146, r3121, r3123
Notice:
The properties of the alarm buffer should be taken from the corresponding product documentation.
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Alarm buffer structure (general principle):
r2122[0], r2124[0], r2123[0], r2125[0] --> alarm 1 (the oldest)
. . .
r2122[7], r2124[7], r2123[7], r2125[7] --> Alarm 8 (the latest)
When the alarm buffer is full, the alarms that have gone are entered into the alarm history:
r2122[8], r2124[8], r2123[8], r2125[8] --> Alarm 1 (the latest)
. . .
r2122[63], r2124[63], r2123[63], r2125[63] --> alarm 56 (the oldest)
r2123[0...63]

Alarm time received in milliseconds / t_alarm recv ms

All objects
Can be changed: -
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the alarm occurred.
Dependency:
Refer to: r2110, r2114, r2122, r2124, r2125, r2134, r2145, r2146, r3121, r3123
Notice:
The time comprises r2145 (days) and r2123 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [ms]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: 8050, 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8050, 8065
Unit selection: -
Expert list: 1
Factory setting
- [ms]