2 Parameters
2.2 List of parameters
The denominator damping can be determined from the equation for the 3 dB bandwidth:
f_3dB bandwidth = 2 * D_denominator * f_bandstop frequency
p1658[0...n]
Current setpoint filter 1 denominator natural frequency / I_set_filt 1 fn_d
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.5 [Hz]
Description:
Sets the denominator natural frequency for current setpoint filter 1 (PT2, general filter).
Dependency:
The current setpoint filter 1 is activated via p1656.0 and parameterized via p1657 ... p1661.
p1659[0...n]

Current setpoint filter 1 denominator damping / I_set_filt 1 D_d

VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.001
Description:
Sets the denominator damping for current setpoint filter 1.
Dependency:
The current setpoint filter 1 is activated via p1656.0 and parameterized via p1657 ... p1661.
p1660[0...n]
Current setpoint filter 1 numerator natural frequency / I_set_filt 1 fn_n
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.5 [Hz]
Description:
Sets the numerator natural frequency for current setpoint filter 1 (general filter).
Dependency:
The current setpoint filter 1 is activated via p1656.0 and parameterized via p1657 ... p1661.
p1661[0...n]

Current setpoint filter 1 numerator damping / I_set_filt 1 D_n

VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.000
Description:
Sets the numerator damping for current setpoint filter 1.
Dependency:
The current setpoint filter 1 is activated via p1656.0 and parameterized via p1657 ... p1661.
p1662[0...n]
Current setpoint filter 2 type / I_set_filt 2 type
VECTOR_G (n/M)
Can be changed: U, T
Data type: Integer16
P-Group: Closed-loop control
Not for motor type: REL
Min
1
Description:
Sets the current setpoint filter 2 as low pass (PT2) or general 2nd-order filter.
Value:
1:
2:
408
PT2 low pass
General 2nd order filter
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
16000.0 [Hz]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
10.000
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
16000.0 [Hz]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
10.000
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
2
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 5710, 6710
Unit selection: -
Expert list: 1
Factory setting
1999.0 [Hz]
Access level: 3
Func. diagram: 5710, 6710
Unit selection: -
Expert list: 1
Factory setting
0.700
Access level: 3
Func. diagram: 5710, 6710
Unit selection: -
Expert list: 1
Factory setting
1999.0 [Hz]
Access level: 3
Func. diagram: 5710, 6710
Unit selection: -
Expert list: 1
Factory setting
0.700
Access level: 3
Func. diagram: 5710, 6710
Unit selection: -
Expert list: 1
Factory setting
1