Topology Comparison Acknowledge Differences / Topo_Compare Ackn; Device Specialization / Specialization - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

- component number of the associated/linked component
- number of the associated/linked port
- component number of the associated/linked component
- number of the associated port, etc.
Data on the next component:
- etc.
Dependency:
Refer to: p9902
Note:
The target topology can only be modified using the commissioning software.
The parameter is not displayed for the STARTER commissioning software.
Changes only become effective when the state of p0009 = 101 changes to 0 or 111.
p9904

Topology comparison acknowledge differences / Topo_compare ackn

CU_G130_DP,
Can be changed: C1(1)
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: Topology
CU_G150_PN
Not for motor type: -
Min
0000 hex
Description:
If, when comparing the actual topology and target topology, only error has occurred, that can be acknowledged, then
using this parameter, a new comparison can be started - acknowledging the error in the target topology.
Differences that can be acknowledged:
- topology comparison, component shifted
- topology comparison, serial number of a component has been detected to be different (byte 3 = 1)
- topology comparison shows one component that is connected differently
The following parameter values are available:
p9904 = 1 --> the procedure is started.
p9904 = 0 after starting --> the procedure has been successfully completed.
p9904 = 1 after starting --> the procedure has not been successfully completed.
The possible causes for an unsuccessful procedure are located in bytes 4, 3, 2.
Byte 2:
Number of structural differences.
Byte 3:
Number of differences that can be acknowledged (p9904).
Byte 4:
Number of differences. These differences can be resolved as follows:
- sets the topology comparison (p9906 or p9907/p9908).
- change over the actual topology.
The appropriate action should be selected corresponding to the message that is displayed/output.
Note:
In order to permanently accept the acknowledgement of the fault that can be resolved, then it must be saved in a
non-volatile fashion (p0977).
p9905

Device specialization / Specialization

CU_G130_DP,
Can be changed: C1(1)
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: Topology
CU_G150_PN
Not for motor type: -
Min
0
Description:
With p9905 = 1, the serial numbers and the hardware versions of all of the components are transferred from the
actual topology into the target topology and a new comparison is started.
For this device specialization, the components of the target topology may only differ from those of the actual topology
by the serial numbers.
With p9905 = 2, the serial numbers, the hardware versions and the order numbers of all of the components are
transferred from the actual topology into the target topology and a new comparison is started.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
FFFF FFFF hex
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 hex
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
949