p7040[0...n]
Par_circuit correction valve lockout time phase U / Comp t_lockout U
VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
-1000000.00 [µs]
Description:
For the particular Motor Module, the correction time must be added to the valve lockout time to be compensated for
phase U (p1828).
The corrective value is used to compensate variations/spread in the valve lockout times of Motor Modules for a
parallel circuit configuration.
Dependency:
Refer to: p1828
p7042[0...n]
Par_circuit correction valve lockout time phase V / Comp t_lockout V
VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
-1000000.00 [µs]
Description:
For the particular Motor Module, the correction time must be added to the valve lockout time to be compensated for
phase V (p1829).
The corrective value is used to compensate variations/spread in the valve lockout times of Motor Modules for a
parallel circuit configuration.
Dependency:
Refer to: p1829
p7044[0...n]
Par_circuit correction valve lockout time phase W / Comp t_lockout W
VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
-1000000.00 [µs]
Description:
For the particular Motor Module, the correction time must be added to the valve lockout time to be compensated for
phase W (p1830).
The corrective value is used to compensate variations/spread in the valve lockout times of Motor Modules for a
parallel circuit configuration.
Dependency:
Refer to: p1830
r7050[0...n]
Par_circuit circulating current phase U / Circ_I_phase U
VECTOR_G (Parallel) Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [A]
Description:
Displays the circulating current of phase U as peak value.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: PDS, p0120
Units group: -
Scaling: -
Max
1000000.00 [µs]
Calculated: -
Dyn. index: PDS, p0120
Units group: -
Scaling: -
Max
1000000.00 [µs]
Calculated: -
Dyn. index: PDS, p0120
Units group: -
Scaling: -
Max
1000000.00 [µs]
Calculated: -
Dyn. index: PDS, p0120
Units group: 6_5
Scaling: p2002
Max
- [A]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [µs]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [µs]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [µs]
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
- [A]
705