Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited. The inhibited interconnections can only be changed again after setting value 999.
p0922
IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
VECTOR_G (n/M)
Can be changed: C2(1), T
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
1
Description:
Sets the send and receive telegram.
Value:
1:
2:
3:
4:
20:
220:
352:
999:
Caution:
Telegrams 2, 3 and 4 are not suitable for sensorless vector control (p1300 = 20). For sensorless vector control, it is
necessary that the setpoint speed is entered at the ramp-function generator input (e.g. p1070) and not after the
ramp-function generator (p1155).
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited. The inhibited interconnections can only be changed again after setting value 999.
r0924[0...1]
ZSW bit pulses enabled / ZSW pulse enab
VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
-
Description:
Displays the position of the "Pulses enabled" status signal in the PROFIdrive telegram.
Index:
[0] = Signal number
[1] = Bit position
p0925
PROFIdrive clock synchronous sign-of-life tolerance / PD SoL_tol
ENC, VECTOR_G
Can be changed: U, T
(n/M)
Data type: Unsigned16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Sets the number of tolerated consecutive sign-of-life errors of the clock-cycle synchronous master.
The sign-of-life signal is normally received in PZD4 (control word 2) from the master.
Dependency:
Refer to: p2045, r2065
Note:
The sign-of-life monitoring is disabled for p0925 = 65535.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Standard telegram 1, PZD-2/2
Standard telegram 2, PZD-4/4
Standard telegram 3, PZD-5/9
Standard telegram 4, PZD-6/14
Standard telegram 20, PZD-2/6
SIEMENS telegram 220, PZD-10/10
SIEMENS telegram 352, PZD-6/6
Free telegram configuration with BICO
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
999
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
65535
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 2401, 2415,
2416, 2419, 2420, 2421, 2422,
2423
Unit selection: -
Expert list: 1
Factory setting
999
Access level: 3
Func. diagram: 2454, 2456
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
1