Mot_Temp_Mod 2/Kty Alarm Threshold / Mod 2/Kty A Thresh; Mot_Temp_Mod 1/2 Threshold / Mod 1/2 Threshold; Mot_Temp_Mod 2/Kty Timer / Mod 2/Kty T_Timer - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Note:
When using a Terminal Module 31 (TM31), the following applies:
- the sensor type used is set using p4100.
- the temperature signal is interconnected using CO: r4105.
p0604[0...n]

Mot_temp_mod 2/KTY alarm threshold / Mod 2/KTY A thresh

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.0 [°C]
Description:
Sets the alarm threshold for monitoring the motor temperature for motor temperature model 2 or KTY.
After the alarm threshold is exceeded, alarm A07910 is output and timer (p0606) is started.
If the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011
is output.
Dependency:
Refer to: p0606, p0612
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis is 2 K.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0605[0...n]

Mot_temp_mod 1/2 threshold / Mod 1/2 threshold

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.0 [°C]
Description:
Sets the threshold for monitoring the motor temperature for motor temperature model 1/2 or KTY.
Motor temperature model 1 (p0612.0 = 1): alarm threshold
- Alarm A07012 is output after the alarm threshold is exceeded.
Motor temperature model 2 (p0612.1 = 1) or KTY: fault threshold
- Fault F07011 is output after the fault threshold is exceeded.
Dependency:
Refer to: p0606, p0611, p0612
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Motor temperature model 1:
p0605 also defines the target temperature of the model for r0034 = 100 %. Therefore, p0605 has no influence on the
time up to alarm A07012 being issued. The time is only determined by time constant p0611, the actual current and
the reference value p0318. For p0318 = 0, the rated motor current is used as reference value.
Note:
The hysteresis is 2 K.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0606[0...n]

Mot_temp_mod 2/KTY timer / Mod 2/KTY t_timer

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.000 [s]
Description:
Sets the timer for monitoring the motor temperature for motor temperature model 2 or KTY.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: MDS, p0130
Units group: 21_1
Scaling: -
Max
200.0 [°C]
Calculated: -
Dyn. index: MDS, p0130
Units group: 21_1
Scaling: -
Max
200.0 [°C]
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
600.000 [s]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8016
Unit selection: p0505
Expert list: 1
Factory setting
130.0 [°C]
Access level: 2
Func. diagram: 8016, 8017
Unit selection: p0505
Expert list: 1
Factory setting
145.0 [°C]
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]