p8921[0...3]

PN IP address of station / PN IP of stat

CU_G130_PN,
Can be changed: U, T
CU_G150_PN
Data type: Unsigned8
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the IP address for the onboard PROFINET interface on the Control Unit.
The active IP address is displayed in r8931.
Note:
The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
p8922[0...3]

PN Default Gateway of Station / PN Def Gateway

CU_G130_PN,
Can be changed: U, T
CU_G150_PN
Data type: Unsigned8
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the default gateway for the onboard PROFINET interface on the Control Unit.
The active default gateway is displayed in r8932.
Note:
The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
p8923[0...3]

PN Subnet Mask of Station / PN Subnet Mask

CU_G130_PN,
Can be changed: U, T
CU_G150_PN
Data type: Unsigned8
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the subnet mask for the onboard PROFINET interface on the Control Unit.
The active subnet mask is displayed in r8933.
Note:
The interface configuration (p8920 and following) is activated with p8925.
The parameter is not influenced by setting the factory setting.
p8924

PN DHCP Mode / PN DHCP Mode

CU_G130_PN,
Can be changed: U, T
CU_G150_PN
Data type: Unsigned8
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the DHCP mode for the onboard PROFINET interface on the Control Unit.
The active DHCP mode is displayed in r8934.
Notice:
When the DHCP mode is active (p8924 > 0), then PROFINET communication via this interface is no longer possible!
However, the interface can be used by the STARTER/SCOUT commissioning tool.
Note:
The interface configuration (p8920 and following) is activated with p8925.
The active DHCP mode is displayed in parameter r8934.
The parameter is not influenced by setting the factory setting.
If value = 0:
DHCP deactivated.
824
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
3
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0