p2039

Select debug monitor interface / Debug monit select

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: Communications
CU_G150_PN
Not for motor type: -
Min
0
Description:
Sets the serial interface for the debug monitor.
The serial interface for the debug monitor is COM1 (X140) or COM2 (internal).
Value = 0: COM2 (internal)
Value = 1: COM1 (X140), commissioning protocol is de-activated
Value = 2: COM2 (internal)
Value = 3: Reserved
p2040

Fieldbus interface monitoring time / Fieldbus t_monit

CU_G130_DP,
Can be changed: U, T
CU_G150_DP
Data type: FloatingPoint32
P-Group: Communications
Not for motor type: -
Min
0 [ms]
Description:
Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Note:
p2040 = 0:
Monitoring is de-activated.
p2042

PROFIBUS Ident Number / PB Ident No.

CU_G130_DP,
Can be changed: T
CU_G150_DP
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
0
Description:
Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value:
0:
1:
Note:
Every change only becomes effective after a POWER ON.
r2043.0...2

BO: IF1 PROFIdrive PZD state / IF1 PD PZD state

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned8
CU_G150_DP,
P-Group: Communications
CU_G150_PN
Not for motor type: -
Min
-
Description:
Displays the PROFIdrive PZD state.
Bit field:
Bit
00
01
02
Dependency:
Refer to: p2044
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
SINAMICS
VIK-NAMUR
Signal name
Setpoint failure
Clock cycle synchronous operation active
Fieldbus oper
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1999999 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 9310
Unit selection: -
Expert list: 1
Factory setting
100 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
FP
-
-
-
467