p7010

Par_circuit current dissymmetry alarm threshold / i_dissym A thresh

VECTOR_G (Parallel) Can be changed: U, T
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
2 [%]
Description:
Sets the alarm threshold to detect current dissymmetry in the parallel circuit configuration.
The deviation between the measured values and average value is evaluated.
The specified value is referred to the rated power unit current (p7251[0]).
Dependency:
Refer to: r7251
p7011
Par_circuit DC link voltage dissymmetry alarm threshold / Vdc_dissym A thrsh
B_INF (Parallel),
Can be changed: U, T
VECTOR_G (Parallel)
Data type: FloatingPoint32
P-Group: Modulation
Not for motor type: -
Min
2 [%]
Description:
Sets the alarm threshold to detect dissymmetry of the DC link voltages in the parallel circuit configuration.
The deviation between the measured values and average value is evaluated.
The specified value is referred to the rated link voltage.
p7015

Par_circuit holding brake power unit data set / Brake PDS

VECTOR_G (Parallel) Can be changed: T
Data type: Integer16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Sets the power unit data set for a parallel connection via which the holding brake is controlled.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
99:
Dependency:
Refer to: p0120, p0121
Note:
PDS: Power unit Data Set
Example:
3 power units are connected in parallel and the holding brake is connected to power unit 1.
p0120 = 3
p0121[0] = component number of power unit 0
p0121[1] = component number of power unit 1 (with holding brake)
p0121[2] = component number of power unit 2
--> p7015 = 1
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Power unit data set 0
Power unit data set 1
Power unit data set 2
Power unit data set 3
Power unit data set 4
Power unit data set 5
Power unit data set 6
Power unit data set 7
No holding brake connected
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
100 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
100 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
99
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
20 [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10 [%]
Access level: 3
Func. diagram: 2701, 2814
Unit selection: -
Expert list: 1
Factory setting
99