Profidrive Profile Number / Pd Profile Number; System Runtime Relative / T_System Relative; Reset Infeed Parameter / Inf Par Reset - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Device type:
r0964[1] = 5200 --> SINAMICS G150 CU320-2 DP
r0964[1] = 5201 --> SINAMICS G150 CU320-2 PN
r0964[1] = 5210 --> SINAMICS G130 CU320-2 DP
r0964[1] = 5211 --> SINAMICS G130 CU320-2 PN
r0965

PROFIdrive profile number / PD profile number

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: Communications
CU_G150_PN
Not for motor type: -
Min
-
Description:
Displays the PROFIdrive profile number and profile version.
Constant value = 0329 hex.
Byte 1: Profile number = 03 hex = PROFIdrive profile
Byte 2: Profile version = 29 hex = Version 4.1
Note:
When the parameter is read via PROFIdrive, the Octet String 2 data type applies.
p0969

System runtime relative / t_System relative

CU_G130_DP,
Can be changed: T
CU_G130_PN,
Data type: Unsigned32
CU_G150_DP,
P-Group: Displays, signals
CU_G150_PN
Not for motor type: -
Min
0 [ms]
Description:
Displays the system runtime in ms since the last POWER ON.
Note:
The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
p0970

Reset infeed parameter / INF par reset

B_INF
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate a reset of the parameters of an individual infeed unit.
The parameters of the basic commissioning (refer to p0009) are in this case not reset (p0107, p0108, p0121, p0170).
These can only be reset using the factory setting of the complete drive unit (p0976).
The sampling times (p0111, p0112, p0115) are only not reset if this results in a conflict with the basic clock cycle
(p0110).
Value:
0:
1:
100:
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset has been completed if p0970 and p0010 have been set to 0.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Inactive
Start a parameter reset
Start a BICO interconnection reset
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
4294967295 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
100
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
275