Co: Fixed Values [%] / Fixed Values [%]; Co: Fixed Value M [Nm] / Fixed Value M [Nm]; Direct Axis Flux Model Display / Mot Psid Trace - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

r2902[0...14]

CO: Fixed values [%] / Fixed values [%]

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Free function blocks
Not for motor type: -
Min
- [%]
Description:
Display and connector output for frequently used percentage values.
Index:
[0] = Fixed value +0 %
[1] = Fixed value +5 %
[2] = Fixed value +10 %
[3] = Fixed value +20 %
[4] = Fixed value +50 %
[5] = Fixed value +100 %
[6] = Fixed value +150 %
[7] = Fixed value +200 %
[8] = Fixed value -5 %
[9] = Fixed value -10 %
[10] = Fixed value -20 %
[11] = Fixed value -50 %
[12] = Fixed value -100 %
[13] = Fixed value -150 %
[14] = Fixed value -200 %
Dependency:
Refer to: p2900, p2901, p2930
Note:
The signal sources can, for example, be used to interconnect scalings.
p2930[0...n]

CO: Fixed value M [Nm] / Fixed value M [Nm]

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Free function blocks
Not for motor type: REL
Min
-100000.00 [Nm]
Description:
Setting and connector output for a fixed torque value.
Dependency:
Refer to: p2900, p2901, r2902
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can, for example, be used to interconnect a supplementary torque.
r2969[0...6]

Direct axis flux model display / Mot Psid trace

VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: ASM, PEM, REL, FEM Scaling: -
Min
-
Description:
Display of the direct axis flux model of the closed-loop controlled reluctance motor for diagnostic purposes:
Display of the entered direct axis current id:
idx0: current in Arms
Display of the saturation curves of the direct axis flux psid(id, iq):
idx1: flux in Vsrms with respect to the direct axis current for iq = 0
idx2: flux in Vsrms with respect to the direct axis current for iq = 0.5 * p2950
idx3: flux in Vsrms with respect to the direct axis current for iq = p2950
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: DDS, p0180
Units group: 7_1
Scaling: p2003
Max
100000.00 [Nm]
Calculated: -
Dyn. index: -
Units group: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 1021
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 1021
Unit selection: p0505
Expert list: 1
Factory setting
0.00 [Nm]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
551

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents