p0609[0...3]

CI: Motor temperature signal source 3 / Mot_temp S_src 3

VECTOR_G
Can be changed: C2(3), T
Data type: Unsigned32 / FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
-
Description:
Sets signal source 3 to evaluate the motor temperature via a BICO interconnection.
Index:
[0] = Motor temperature channel 1
[1] = Motor temperature channel 2
[2] = Motor temperature channel 3
[3] = Motor temperature channel 4
Dependency:
Refer to: p0600
Note:
Temperature sensor KTY:
Valid temperature range -48 °C ... 248 °C.
Temperature sensor PTC/bimetal:
For a value of -50 °C, the following applies: Motor temperature < nominal response temperature of the PTC (bimetal
contact closed).
For a value of 250 °C, the following applies: Motor temperature >= nominal response temperature of the PTC
(bimetal contact open).
Note:
When using a Terminal Module 120 (TM120), the following applies:
- the sensor type used is set using p4100.
- the temperature signal is interconnected using connector output r4105.
p0610[0...n]

Motor overtemperature response / Mot temp response

VECTOR_G
Can be changed: C2(3), T
Data type: Integer16
P-Group: Motor
Not for motor type: -
Min
0
Description:
Sets the system response when the motor temperature reaches the alarm threshold.
Value:
0:
1:
2:
12:
Dependency:
Refer to: p0601, p0604, p0605, p0614, p0615
Note:
The I_max reduction is not executed for PTC (p0601 = 1) or bimetallic NC contact (p0601 = 4).
The I_max reduction results in a lower output frequency.
If value = 0:
An alarm is output and I_max is not reduced.
If value = 1:
An alarm is output and a timer is started. A fault is output if the alarm is still active after this timer has expired.
- for KTY84, the following applies: I_max. is reduced
- for PTC, the following is valid: I_max. is not reduced
If value = 2:
An alarm is output and a timer is started. A fault is output if the alarm is still active after this timer has expired.
If value = 12:
Behavior is always the same as for value 2.
For motor temperature monitoring without temperature sensor, when switching off, the model temperature is saved in
a non-volatile fashion. When switching on, the same value (reduced by p0614) is taken into account in the model
calculation. As a consequence, the UL508C specification is fulfilled.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
No response only alarm no reduction of I_max
Messages, reduction of I_max
Messages, no reduction of I_max
Messages, no reduction of I_max, temperature storage
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2006
Max
-
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
12
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8016, 8017
Unit selection: -
Expert list: 1
Factory setting
12