Tm150 Delay Time / Tm150 T_Delay; Tm31 Temperature Evaluation Delay Time / Tm31 Temp T_Delay - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Notice:
Fault F35207 only causes the drive to be shut down if there is at least one BICO interconnection between the drive
and TM31.
For p4102[0...1] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" (p4100 = 1), the following applies:
To activate the alarm or fault, p4102[0...1] must be set <= 250 °C.
p4103[0...11]

TM150 delay time / TM150 t_delay

TM150
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.0 [s]
Description:
Sets the delay time for the output of the fault for the Terminal Module 150 (TM150).
The timer is started when the alarm threshold (e.g. p4102[0]) is exceeded.
If the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then the
corresponding fault is output.
The fault can be acknowledged, if, after the delay time has expired, the alarm threshold is again fallen below.
For sensor type "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6) the following applies:
- If the fault threshold (e.g. p4102[1]) is exceeded before the delay time has expired, then the corresponding fault is
immediately output.
For sensor type "PTC thermistor", "Bimetallic NC contact" (p4100[0...11] = 1, 4), the following applies:
- Alarm and fault threshold simultaneously respond. The fault is only issued after the delay time has expired.
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
Refer to: p4102, r4104, r4105, p4118
Warning:
The fault F35207 ... F35210 and F35400 ... 35407 only results in the drive being shut down if at least one BICO
interconnection exists between the drive and the TM150.
Note:
For p4103 = 0 s and sensor type "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6) the following applies:
- The corresponding fault can only be initiated via the fault threshold (output of the timer is always a logical 0).
For p4103 = 0 s and sensor type "PTC thermistor", "Bimetallic NC contact" (p4100[0...11] = 1, 4), the following
applies:
- The corresponding alarm and fault are simultaneously output (delay time = 0 s).
p4103

TM31 temperature evaluation delay time / TM31 temp t_delay

TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.000 [ms]
Description:
Sets the delay time for the output of the fault for the Terminal Module 31 (TM31).
The timer is started when the alarm threshold (p4102[0]) is exceeded.
If the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F35207
is output.
The fault can be acknowledged, if, after the delay time has expired, the alarm threshold is again fallen below.
628
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600.0 [s]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
600000.000 [ms]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
0.0 [s]
Access level: 1
Func. diagram: 9576
Unit selection: -
Expert list: 1
Factory setting
0.000 [ms]
SINAMICS G130/G150