2 Parameters
2.2 List of parameters
Note:
An external fault is triggered with a 1/0 signal.
If this fault is output at the Control Unit, then it is transferred to all existing drive objects.
r2109[0...63]

Fault time removed in milliseconds / t_flt resolved ms

All objects
Can be changed: -
Data type: Unsigned32
P-Group: Messages
Not for motor type: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the fault was removed.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2114, r2130, r2133, r2136, r3115, r3120, r3122
Notice:
The time comprises r2136 (days) and r2109 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
r2110[0...63]

Alarm number / Alarm number

All objects
Can be changed: -
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
-
Description:
This parameter is identical to r2122.
p2111

Alarm counter / Alarm counter

All objects
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Number of alarms that have occurred after the last reset.
Dependency:
When p2111 is set to 0, the following is initiated:
- all of the alarms of the alarm buffer that have gone [0...7] are transferred into the alarm history [8...63].
- the alarm buffer [0...7] is deleted.
Refer to: r2110, r2122, r2123, r2124, r2125
Note:
The parameter is reset to 0 at POWER ON.
p2112[0...n]

BI: External alarm 1 / External alarm 1

B_INF, VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Messages
Not for motor type: -
Min
-
Description:
Sets the signal source for external alarm 1.
Note:
An external alarm is triggered with a 1/0 signal.
506
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
- [ms]
Access level: 2
Func. diagram: 8065
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8050, 8065
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2546
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS G130/G150