[28] = Cam position SCA29 (SN29)
[29] = Cam position SCA30 (SN30)
Dependency:
Refer to: p9501, p9503, p9537
Note:
A change only becomes effective after a POWER ON.
SCA: Safe Cam / SN: Safe software cam
p9536[0...29]

SI Motion SCA (SN) plus cam position (Control Unit) / SI Mtn SCA+

VECTOR_G (Safety
Can be changed: U, T
rot)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
-2147000.000 [°]
Description:
Sets the plus cam position for the function "Safe Cam" (SCA).
Index:
[0] = Cam position SCA1 (SN1)
[1] = Cam position SCA2 (SN2)
[2] = Cam position SCA3 (SN3)
[3] = Cam position SCA4 (SN4)
[4] = Cam position SCA5 (SN5)
[5] = Cam position SCA6 (SN6)
[6] = Cam position SCA7 (SN7)
[7] = Cam position SCA8 (SN8)
[8] = Cam position SCA9 (SN9)
[9] = Cam position SCA10 (SN10)
[10] = Cam position SCA11 (SN11)
[11] = Cam position SCA12 (SN12)
[12] = Cam position SCA13 (SN13)
[13] = Cam position SCA14 (SN14)
[14] = Cam position SCA15 (SN15)
[15] = Cam position SCA16 (SN16)
[16] = Cam position SCA17 (SN17)
[17] = Cam position SCA18 (SN18)
[18] = Cam position SCA19 (SN19)
[19] = Cam position SCA20 (SN20)
[20] = Cam position SCA21 (SN21)
[21] = Cam position SCA22 (SN22)
[22] = Cam position SCA23 (SN23)
[23] = Cam position SCA24 (SN24)
[24] = Cam position SCA25 (SN25)
[25] = Cam position SCA26 (SN26)
[26] = Cam position SCA27 (SN27)
[27] = Cam position SCA28 (SN28)
[28] = Cam position SCA29 (SN29)
[29] = Cam position SCA30 (SN30)
Dependency:
Refer to: p9501, p9503, p9537
Note:
A change only becomes effective after a POWER ON.
SCA: Safe Cam / SN: Safe software cam
p9537[0...29]

SI Motion SCA (SN) plus cam position (Control Unit) / SI Mtn SCA-

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
-2147000.000 [mm]
Description:
Sets the minus cam position for the function "Safe Cam" (SCA).
Index:
[0] = Cam position SCA1 (SN1)
[1] = Cam position SCA2 (SN2)
[2] = Cam position SCA3 (SN3)
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2147000.000 [°]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2147000.000 [mm]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
10.000 [°]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-10.000 [mm]