Vdc_Max Controller Speed Threshold / Vdc_Max N_Thresh; Vdc Controller Proportional Gain / Vdc_Ctrl Kp - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Note:
For SINAMICS GM/SM, the following applies:
Minimum value = 0.75, Maximum value = 0.90
r1246
Vdc_min controller switch-in level (kinetic buffering) / Vdc_min on_level
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: REL
Min
- [V]
Description:
Displays the switch-in level for the Vdc_min controller (kinetic buffering).
Note:
The Vdc_min controller is not switched back off until the DC-link voltage rises above the threshold 1.05 * p1246 and
the controller output is zero.
p1247[0...n]
Vdc_min controller dynamic factor (kinetic buffering) / Vdc_min dyn_factor
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: REL
Min
1 [%]
Description:
Sets the dynamic factor for the Vdc_min controller (kinetic buffering).
100% means that p1250, p1251, and p1252 (gain, integral time, and rate time) are used corresponding to their basic
settings and based on a theoretical controller optimization.
If subsequent optimization is required, this can be carried out using the dynamic factor. In this case p1250, p1251,
p1252 are weighted with the dynamic factor p1247.
If several components are connected to the DC link, then the dynamic factor must be increased corresponding to the
ratio of the additional capacitances to the capacitance of the component involved.
p1249[0...n]

Vdc_max controller speed threshold / Vdc_max n_thresh

VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: REL
Min
0.00 [rpm]
Description:
Sets the lower speed threshold for the Vdc_max controller.
When this speed threshold is undershot, the Vdc_max control is switched out and the speed is controlled using the
ramp-function generator.
Note:
For fast braking where the ramp-function generator tracking was active, it is possible to prevent the drive rotating in
the opposite direction by increasing the speed threshold and setting a final rounding-off time in the ramp-function
generator (p1131). This is supported using a dynamic setting of the speed controller.
p1250[0...n]

Vdc controller proportional gain / Vdc_ctrl Kp

VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: REL
Min
0.00
Description:
Sets the proportional gain for the DC-link voltage controller (Vdc_min controller, Vdc_max controller).
Dependency:
The effective proportional gain is obtained taking into account p1243 (Vdc_max controller dynamic factor).
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2001
Max
- [V]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
10000 [%]
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: -
Max
210000.00 [rpm]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.00
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6220
Unit selection: -
Expert list: 1
Factory setting
- [V]
Access level: 3
Func. diagram: 6220
Unit selection: -
Expert list: 1
Factory setting
100 [%]
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
10.00 [rpm]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1.00
335