r0082
CO: Active power actual value / P_act
B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [kW]
Description:
Displays the instantaneous active power.
Dependency:
Refer to: r0032
Notice:
For Basic Line Modules of chassis format, the displayed value is invalid as these units do not have any current
sensing.
Note:
The active power is available smoothed (r0032) and unsmoothed (r0082).
r0082[0...2]
CO: Active power actual value / P_act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [kW]
Description:
Displays the instantaneous active power.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Electric power
Dependency:
Refer to: r0032
Note:
The mechanical active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed
(r0082[0]).
r0083
CO: Flux setpoint / Flex setp
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [%]
Description:
Displays the flux setpoint.
r0084[0...1]
CO: Flux actual value / Flux act val
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [%]
Description:
Displays the flux actual value.
Index:
[0] = Unsmoothed
[1] = Smoothed
Note:
The flux actual value (index 1) smoothed with p1585 is only displayed for separately-excited synchronous motors. In
the following cases, the unsmoothed flux actual value is also displayed:
- in the range of the current model.
- during the pole position identification.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: 14_7
Scaling: r2004
Max
- [kW]
Calculated: -
Dyn. index: -
Units group: 14_5
Scaling: r2004
Max
- [kW]
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: PERCENT
Max
- [%]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 8750, 8850,
8950
Unit selection: p0505
Expert list: 1
Factory setting
- [kW]
Access level: 3
Func. diagram: 6714, 6799
Unit selection: p0505
Expert list: 1
Factory setting
- [kW]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 6726, 6730,
6732
Unit selection: -
Expert list: 1
Factory setting
- [%]
67