U/F Mode Resonance Damping Gain / Uf Res_Damp Gain; U/F Mode Resonance Damping Filter Time Constant / Uf Res_Damp T; I_Max Frequency Controller Proportional Gain / I_Max_Ctrl Kp - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Dependency:
p1335 > 0 %: Slip compensation active.
Refer to: p1335
p1338[0...n]

U/f mode resonance damping gain / Uf Res_damp gain

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: U/f open-loop control
Not for motor type: -
Min
0.00
Description:
Sets the gain for resonance damping for U/f control.
Dependency:
Refer to: p1300, p1339, p1349
Note:
The resonance damping function dampens active current oscillations that frequency occur under no-load conditions.
The resonance damping is active in a range from approximately 6 % of the rated motor frequency (p0310). The
shutoff frequency is determined by p1349.
For the open-loop control modes p1300 = 5 and 6 (textile sectors), the resonance damping is internally disabled in
order that the output frequency can be precisely set.
p1339[0...n]

U/f mode resonance damping filter time constant / Uf Res_damp T

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: U/f open-loop control
Not for motor type: -
Min
1.00 [ms]
Description:
Sets the filter time constant for resonance damping for U/f control.
Dependency:
Refer to: p1300, p1338, p1349
p1340[0...n]

I_max frequency controller proportional gain / I_max_ctrl Kp

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: U/f open-loop control
Not for motor type: -
Min
0.000
Description:
Sets the proportional gain of the I_max frequency controller.
The I_max controller reduces the drive converter output current if the maximum current (r0067) is exceeded.
In the U/f operating modes (p1300) for the I_max control, one controller is used that acts on the output frequency and
one controller that acts on the output voltage. The frequency controller reduces the current by decreasing the
converter output frequency. The frequency is reduced down to a minimum value (equaling twice rated slip). If the
overcurrent condition cannot be successfully resolved using this measure, then the drive converter output voltage is
reduced using the I_max voltage controller. Once the overcurrent condition has been resolved, the drive is
accelerated along the ramp set in p1120 (ramp-up time).
Dependency:
In the U/f modes (p1300) for textile applications and for external voltage setpoints, only the I_max voltage controller
is used.
Notice:
When de-activating the I_max controller, the following must be carefully observed:
When the maximum current (r0067) is exceeded, the output current is no longer reduced. The drive is switched off
when the overcurrent limits are exceeded.
Note:
The I_max limiting controller becomes ineffective if the ramp-function generator is de-activated with p1122 = 1.
p1341 = 0: I_max frequency controller de-activated and I_max voltage controller activated over the complete speed
range.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
100.00
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
1000.00 [ms]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
0.500
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6300, 6310
Unit selection: -
Expert list: 1
Factory setting
0.00
Access level: 3
Func. diagram: 6310
Unit selection: -
Expert list: 1
Factory setting
20.00 [ms]
Access level: 3
Func. diagram: 6300
Unit selection: -
Expert list: 1
Factory setting
0.000
355

Hide quick links: