2 Parameters
2.2 List of parameters
p3883

BI: ESM direction of rotation signal source / ESM rot dir s s

VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the signal source for the direction of rotation during essential service mode (ESM).
p3883 = 1 signal:
Direction of rotation of the setpoint, parameterized for essential service mode, is reversed.
p3883 = 0 signal:
Direction of rotation of the setpoint parameterized for essential service mode is kept.
Note:
ESM: Essential Service Mode
p3886

CI: ESM setpoint TB30/TM31 analog input / ESM setp TB30TM31

VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the signal source for the setpoint for p3881 = 5 (TB30/TM31 analog input) in the essential service mode (ESM).
Dependency:
Refer to: p3881
Note:
ESM: Essential Service Mode
r3887[0...1]

ESM number of activations/faults / ESM act/fault qty

VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Functions
Not for motor type: -
Min
-
Description:
Displays the number of activations and faults that have occurred for the essential service mode (ESM).
Index:
[0] = Activation of the essential service mode
[1] = Faults during the essential service mode
Dependency:
Refer to: p3888
Note:
ESM: Essential Service Mode
p3888

ESM reset number of activations/faults / ESM act/F qty r

VECTOR_G
Can be changed: T
Data type: Unsigned8
P-Group: Functions
Not for motor type: -
Min
0
Description:
Setting to reset the number of activations and faults that have occurred for the essential service mode (ESM).
1: counter reset active (r3887[0, 1])
0: inactive
Dependency:
Refer to: r3887
Note:
ESM: Essential Service Mode
The parameter is automatically reset to zero after the counter has been reset.
592
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2000
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 7033
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 7033
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: 7033
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 4
Func. diagram: 7033
Unit selection: -
Expert list: 1
Factory setting
0