2 Parameters
2.2 List of parameters
This timer is started when the temperature alarm threshold (p0604) is exceeded.
If the timer has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011 is
output.
If the temperature fault threshold (p0605) is prematurely exceeded before the timer has expired, then fault F07011 is
immediately output.
Dependency:
Refer to: p0604, p0605
Note:
With p0606 = 0 s, the timer is de-activated and only the fault threshold is effective.
KTY sensor: When setting the minimum value, the timer is disabled and a fault is not output until p0605 is exceeded.
PTC sensor, bimetallic NC contact: The timer minimum value has no special significance.
p0607[0...n]

Temperature sensor fault timer / Sensor fault time

VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.000 [s]
Description:
Sets the timer between the output of alarm and fault for a temperature sensor fault.
If there is a sensor fault, this timer is started.
If the sensor fault is still present after the timer has expired, a corresponding fault is output.
Notice:
The parameterized time is internally rounded-off to an integer multiple of 48 ms.
Note:
If the motor is an induction motor, the timer is switched off when setting the minimum value and no alarm is output.
Temperature monitoring is then based on the thermal model.
p0608[0...3]

CI: Motor temperature signal source 2 / Mot_temp S_src 2

VECTOR_G
Can be changed: C2(3), T
Data type: Unsigned32 / FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
-
Description:
Sets signal source 2 to evaluate the motor temperature via a BICO interconnection.
Index:
[0] = Motor temperature channel 1
[1] = Motor temperature channel 2
[2] = Motor temperature channel 3
[3] = Motor temperature channel 4
Dependency:
Refer to: p0600
Note:
Temperature sensor KTY:
Valid temperature range -48 °C ... 248 °C.
Temperature sensor PTC/bimetal:
For a value of -50 °C, the following applies: Motor temperature < nominal response temperature of the PTC (bimetal
contact closed).
For a value of 250 °C, the following applies: Motor temperature >= nominal response temperature of the PTC
(bimetal contact open).
Note:
When using a Terminal Module 120 (TM120), the following applies:
- the sensor type used is set using p4100.
- the temperature signal is interconnected using connector output r4105.
220
Calculated: -
Dyn. index: MDS, p0130
Units group: -
Scaling: -
Max
600.000 [s]
Calculated: -
Dyn. index: -
Units group: -
Scaling: p2006
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0.100 [s]
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0