2 Parameters
2.2 List of parameters
p3109

RTC real time synchronization tolerance window / RTC sync tol

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: -
CU_G150_PN
Not for motor type: -
Min
0 [ms]
Description:
Sets the tolerance window for time synchronization.
When this tolerance window is exceeded, an appropriate alarm is output.
p3110

External fault 3 power-up delay / Ext fault 3 t_on

All objects
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0 [ms]
Description:
Sets the delay time for external fault 3.
Dependency:
Refer to: p2108, p3111, p3112
p3111[0...n]

BI: External fault 3 enable / Ext fault 3 enab

B_INF, VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Messages
Not for motor type: -
Min
-
Description:
Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3112
p3111
BI: External fault 3 enable / Ext fault 3 enab
CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned32 / Binary
CU_G150_DP,
P-Group: Messages
CU_G150_PN, ENC,
Not for motor type: -
HUB, TB30, TM150,
TM31, TM54F_MA,
Min
TM54F_SL
-
Description:
Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p2108, p3110, p3112
554
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1000 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1000 [ms]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100 [ms]
Access level: 3
Func. diagram: 2546
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2546
Unit selection: -
Expert list: 1
Factory setting
1