p1203[0...n]

Flying restart search rate factor / FlyRst v_Srch Fact

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: PEM, REL
Min
10 [%]
Description:
Sets the factor for the search speed for flying restart.
The value influences the rate at which the output frequency is changed during a flying restart . A higher value results
in a longer search time.
Recommend.:
For encoderless vector control and motor cables longer than 200 m, set the factor p1203 >= 300 %.
Caution:
An unfavorable parameter value can result in the motor behaving in an uncontrollable fashion.
For vector control, a value that is too low or too high can cause flying restart to become unstable.
Note:
The parameter factory setting is selected so that standard induction motors that are rotating can be found and
restarted as quickly as possible (fast flying restart).
With this pre-setting, if the motor is not found (e.g. for motors that are accelerated as a result of active loads or with
U/f control and low speeds), we recommend that the search rate is reduced (by increasing p1203).
This parameter is not relevant for a fast flying restart with voltage model (see r1780.11).
r1204.0...15

CO/BO: Flying restart U/f control status / FlyRest Uf st

VECTOR_G
Can be changed: -
Data type: Unsigned16
P-Group: Functions
Not for motor type: PEM, REL
Min
-
Description:
Displays the status for checking and monitoring flying restart states in the U/f control mode.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
r1205.0...20

CO/BO: Flying restart vector control status / FlyRest vector st

VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Functions
Not for motor type: PEM, REL
Min
-
Description:
Display and connector output for the status for checking and monitoring flying restart states in the vector control
mode.
314
Signal name
Current impressed
No current flow
Voltage input
Voltage reduced
Start ramp-function generator
Wait for execution
Slope filter act
Positive gradient
Current < thresh
Current minimum
Search in the positive direction
Stop after positive direction
Stop after negative direction
No result
Fast flying restart w/ voltage model for
induction motor activ.
Flying restart with VSM active
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
4000 [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100 [%]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents