p4686[0...n]

Zero mark minimum length / ZM min length

ENC, VECTOR_G
Can be changed: C2(4)
Data type: Unsigned32
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Sets the minimum length for the zero mark in 1/4 encoder pulses.
Dependency:
Refer to: p0425, p0437
Note:
The value for the minimum length of the zero mark must be set less than p0425.
The parameter is activated using p0437.1 = 1 (zero mark edge detection).
p4688

CO: Zero mark monitoring differential pulse count / ZM diff_pulse qty

ENC
Can be changed: T
Data type: Integer32
P-Group: -
Not for motor type: -
Min
-2147483648
Description:
Displays the number of differential pulses for the zero mark monitoring that have accumulated.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688).
Dependency:
Refer to: p4681, p4682, p4683, p4684
Note:
The display can only be reset to zero.
p4688[0...2]
CO: Zero mark monitoring differential pulse count / ZM diff_pulse qty
VECTOR_G
Can be changed: T
Data type: Integer32
P-Group: -
Not for motor type: -
Min
-2147483648
Description:
Displays the number of differential pulses for the zero mark monitoring that have accumulated.
If fault F3x131 is re-parameterized to alarm (A) or no message (N), the encoder pulses which have not been
corrected are added to the accumulator (p4688).
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency:
Refer to: p4681, p4682, p4683, p4684
Note:
The display can only be reset to zero.
r4689

CO: Squarewave encoder diagnostics / Sq-wave enc diag

ENC
Can be changed: -
Data type: Unsigned32
P-Group: Encoder
Not for motor type: -
Min
-
Description:
Displays the encoder status according to PROFIdrive for a squarewave encoder.
Note:
After alarm A3x422 is output, this parameter is set for 100 ms.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: EDS, p0140
Units group: -
Scaling: -
Max
10
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2147483647
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2147483647
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-