2 Parameters
2.2 List of parameters
p1138[0...n]

CI: Ramp-function generator ramp-up time scaling / RFG t_RU scal

VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for scaling the ramp-up time of the ramp-function generator.
Dependency:
Refer to: p1120
Note:
The ramp-up time is set in p1120.
p1139[0...n]

CI: Ramp-function generator ramp-down time scaling / RFG t_RD scal

VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for scaling the ramp-down time of the ramp-function generator.
Dependency:
Refer to: p1121
Note:
The ramp-down time is set in p1121.
p1140[0...n]
BI: Enable ramp-function generator/inhibit ramp-function generator / RFG enable
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Ramp-function generator enable.
Dependency:
Refer to: p1141, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1141[0...n]
BI: Continue ramp-function generator/freeze ramp-function generator / Continue RFG
VECTOR_G
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "continue ramp-function generator/freeze ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 5 (STW1.5).
BI: p1141 = 0 signal:
Freezes the ramp-function generator.
306
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 3060, 3070
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 3060, 3070
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2501
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 2501
Unit selection: -
Expert list: 1
Factory setting
1