Actual Power Unit Type / Pu Actual Type - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Note:
The parameter is used to identify when the drive is being commissioned for the first time.
The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers are
identical (p0010 = 2).
For parallel circuit configurations, the parameter index is assigned to a power unit.
p0201[0...n]
Power unit code number / PU code no
VECTOR_G
Can be changed: C2(2)
Data type: Unsigned16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Sets the actual code number from r0200 to acknowledge the power unit being used.
When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.
Notice:
When p0201 = 10000, the rated power unit data is reloaded and dependent parameters are set (e.g. p0205, p0210,
p0230, p0857, p1800). p0201 is then automatically assigned the value of r0200 if the code number of the power unit
could be read. A warm start must be performed after this procedure (automatically if necessary).
Note:
The parameter is used to identify when the drive is being commissioned for the first time.
The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers are
identical (p0010 = 2). However, if the comparator in p9906 or p9908 is at 2 (low) or 3 (minimum), the power unit
commissioning is automatically set to p0201 = r0200 upon exiting.
When the code number is changed, the connection voltage (p0210) is checked and, if necessary, adjusted.
For parallel circuit configurations, the parameter index is assigned to a power unit.
r0203[0...n]

Actual power unit type / PU actual type

B_INF, VECTOR_G
Can be changed: -
Data type: Integer16
P-Group: Converter
Not for motor type: -
Min
2
Description:
Displays the type of power unit found.
Value:
2:
3:
4:
5:
6:
7:
100:
101:
102:
103:
112:
113:
114:
115:
116:
118:
120:
126:
130:
133:
135:
136:
137:
138:
150:
151:
200:
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
MICROMASTER 440
MICROMASTER 411
MICROMASTER 410
MICROMASTER 436
MICROMASTER 440 PX
MICROMASTER 430
SINAMICS S
SINAMICS S (value)
SINAMICS S (combi)
SINAMICS S120M (distributed)
PM220 (SINAMICS G120)
PM230 (SINAMICS G120)
PM240 (SINAMICS G120)
PM250 (SINAMICS G120 / S120)
PM260 (SINAMICS G120)
SINAMICS G120 Px
PM340 (SINAMICS S120)
SINAMICS ET200PRO
PM250D (SINAMICS G120D)
SINAMICS G120C
SINAMICS PMV40
SINAMICS PMV60
SINAMICS PMV80
SINAMICS G110M
SINAMICS G
PM330 (SINAMICS G120)
SINAMICS GM
Calculated: -
Dyn. index: PDS, p0120
Units group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: PDS, p0120
Units group: -
Scaling: -
Max
400
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
101