Si Tm54F Emergency Stop Input Terminal / Si E-Stop F-Di; Si Tm54F Safe State Signal Selection / Si Safe State Sel - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Index:
[0] = Drive group 1
[1] = Drive group 2
[2] = Drive group 3
[3] = Drive group 4
Note:
Parameter being prepared. For this firmware version, the function interface is not supported.
If value = 0:
No terminal assigned, no static agreement.
If value = 255:
No terminal assigned, static agreement.
p10038[0...3]

SI TM54F Emergency Stop input terminal / SI E-Stop F-DI

TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the input terminal for input "Emergency Stop" (operating mode "function interface").
The behavior of this input signal is set in p10021.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
255:
Index:
[0] = Drive group 1
[1] = Drive group 2
[2] = Drive group 3
[3] = Drive group 4
Dependency:
Refer to: p10008, p10021
Note:
Parameter being prepared. For this firmware version, the function interface is not supported.
If value = 0:
No terminal assigned, "Emergency Stop" statically active.
If value = 255:
No terminal assigned, no "Emergency Stop" statically active.
p10039[0...3]

SI TM54F Safe State signal selection / SI Safe State Sel

TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Index:
[0] = Drive group 1
[1] = Drive group 2
[2] = Drive group 3
[3] = Drive group 4
Bit field:
Bit
00
01
02
03
982
Statically active
F-DI 0 (X521.2/3/6)
F-DI 1 (X521.4/5/7)
F-DI 2 (X522.1/2/7)
F-DI 3 (X522.3/4/8)
F-DI 4 (X522.5/6/9)
F-DI 5 (X531.2/3/6)
F-DI 6 (X531.4/5/7)
F-DI 7 (X532.1/2/7)
F-DI 8 (X532.3/4/8)
F-DI 9 (X532.5/6/9)
Statically inact
Signal name
Power_removed
SS1_active
SS2_active
SOS_active
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Selected
Selected
Selected
Selected
List Manual (LH2), 04/2014, A5E03263479A
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2856
Unit selection: -
Expert list: 1
Factory setting
0000 0001 bin
0 signal
Not selected
Not selected
Not selected
Not selected
SINAMICS G130/G150
FP
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents