Bi: External Alarm 3 / External Alarm 3; Change Message Type Message Number / Chng Type Msg_No; Change Message Type Type / Change Type Type - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p2117[0...n]

BI: External alarm 3 / External alarm 3

B_INF, VECTOR_G
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Messages
Not for motor type: -
Min
-
Description:
Sets the signal source for external alarm 3.
Note:
An external alarm is triggered with a 1/0 signal.
p2117
BI: External alarm 3 / External alarm 3
CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned32 / Binary
CU_G150_DP,
P-Group: Messages
CU_G150_PN, ENC,
Not for motor type: -
HUB, TB30, TM150,
TM31, TM54F_MA,
Min
TM54F_SL
-
Description:
Sets the signal source for external alarm 3.
Note:
An external alarm is triggered with a 1/0 signal.
p2118[0...19]

Change message type message number / Chng type msg_no

All objects
Can be changed: U, T
Data type: Unsigned16
P-Group: Messages
Not for motor type: -
Min
0
Description:
Selects faults or alarms for which the message type should be changed.
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2119
Note:
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
p2119[0...19]

Change message type type / Change type type

All objects
Can be changed: U, T
Data type: Integer16
P-Group: Messages
Not for motor type: -
Min
1
Description:
Sets the message type for the selected fault or alarm.
Value:
1:
2:
3:
Dependency:
Selects the fault or alarm selection and sets the required type of message realized under the same index.
Refer to: p2118
Note:
Re-parameterization is also possible if a message is present. The change only becomes effective after the message
has gone.
The message type can only be changed for messages with the appropriate identification (exception, value = 0).
Example:
F12345(A) --> Fault F12345 can be changed to alarm A12345.
In this case, the message number that may be possibly entered in p2100[0...19] and p2126[0...19] is automatically
removed.
508
Fault (F)
Alarm (A)
No message (N)
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
3
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 2546
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 8050, 8075
Unit selection: -
Expert list: 1
Factory setting
1