p4650

Encoder functional reserve component number / Enc fct_res num

CU_G130_DP,
Can be changed: U, T
CU_G130_PN,
Data type: Unsigned16
CU_G150_DP,
P-Group: Displays, signals
CU_G150_PN
Not for motor type: -
Min
0
Description:
Sets the component number (p0141) of the encoder whose functional reserve is to be displayed (r4651).
Dependency:
Refer to: r4651
r4651[0...3]

Encoder functional reserve / Enc fct_reserve

CU_G130_DP,
Can be changed: -
CU_G130_PN,
Data type: FloatingPoint32
CU_G150_DP,
P-Group: Displays, signals
CU_G150_PN
Not for motor type: -
Min
- [%]
Description:
Displays the functional reserve of the encoder selected via p4650.
0 ... 25 %:
The function limit has been reached. A service is recommended.
26 ... 100 %:
The encoder is working in the specified range.
Index:
[0] = Function reserve 1
[1] = Function reserve 2
[2] = Function reserve 3
[3] = Function reserve 4
Dependency:
Refer to: p4650
Note:
Value = 999 means:
- the component specified in p4650 is not connected
- the encoder does not support the display of the functional reserve
p4652

XIST1_ERW reset mode / XIST1_ERW res mode

ENC
Can be changed: C1(3)
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the mode to reset the actual value in XIST_ERW (CO: r4653).
Value:
0:
1:
2:
3:
Dependency:
Refer to: r4653, r4654, p4655
Note:
If value = 1:
The value in XIST1_ERW is reset when passing every zero mark.
If value = 2:
The value in XIST1_ERW is reset with a 0/1 edge via binector input p4655.
If value = 3:
The value in XIST1_ERW is reset after a 0/1 edge via binector input p4655 when passing the next zero mark.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Inactive
Reset with zero mark
Reset with BICO
Reset with selected zero mark
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
399
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
- [%]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
3
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 4750
Unit selection: -
Expert list: 1
Factory setting
0
641