2 Parameters
2.2 List of parameters
p3206[0...n]

Flux outside tolerance delay time / Flux n tol t_del

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PEM, REL
Min
0.0 [s]
Description:
Sets the delay time for the "flux outside tolerance" message for the flux monitoring.
Dependency:
Refer to: p3204, p3205
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The flux monitoring is only active after magnetizing (r0056.4 = 1).
p3207[0...n]

Zero current signal threshold value / I_0_sig thresh

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PEM, REL
Min
0.01 [Arms]
Description:
Sets the threshold value for the zero current signal for the zero current monitoring.
If the absolute current falls below the threshold value then r2199.6 is set to 1 after the delay time has expired. The bit
is reset if the threshold value and the hysteresis are exceeded again.
Dependency:
Refer to: r2199, p3208, p3209
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold value in p2161 (r2199.0 = 1).
p3208[0...n]

Zero current signal hysteresis / I_0_sig hyst

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PEM, REL
Min
0.01 [Arms]
Description:
Sets the hysteresis for the zero current signal for the zero current monitoring.
Dependency:
Refer to: p3207, p3209
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold value in p2161 (r2199.0 = 1).
p3209[0...n]

Zero current signal delay time / I_0_sig t_del

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Messages
Not for motor type: ASM, PEM, REL
Min
0.00 [s]
Description:
Sets the delay time for the zero current signal for the zero current monitoring.
Dependency:
Refer to: p3207, p3208
Note:
The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold in p2161 (r2199.0 = 1).
562
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
10.0 [s]
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Units group: 6_2
Scaling: -
Max
10000.00 [Arms]
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Units group: 6_2
Scaling: -
Max
10000.00 [Arms]
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
10.00 [s]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
5.0 [s]
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
1.00 [Arms]
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
1.00 [Arms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.02 [s]
SINAMICS G130/G150