2 Parameters
2.2 List of parameters
p2263

Technology controller type / Tec_ctrl type

VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Integer16
P-Group: Technology
Not for motor type: -
Min
0
Description:
Sets the type of technology controller.
Value:
0:
1:
p2264[0...n]

CI: Technology controller actual value / Tec_ctrl act val

VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source for the actual value of the technology controller.
p2265
Technology controller actual value filter time constant / Tec_ctrl act T
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.000 [s]
Description:
Sets the time constant for the actual value filter (PT1) of the technology controller.
r2266
CO: Technology controller actual value after filter / Tec_ctr act aftFlt
VECTOR_G
Can be changed: -
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
- [%]
Description:
Display and connector output for the smoothed actual value after the filter (PT1) of the technology controller.
p2267
Technology controller upper limit actual value / Tec_ctrl u_lim act
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-10000.00 [%]
Description:
Sets the upper limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2252, p2264, p2265, p2271
Notice:
If the actual value exceeds this upper limit, this results in fault F07426.
Note:
Limiting only active for p2252.3 = 1.
538
D component in the actual value signal
D component in the fault signal
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
60.000 [s]
Calculated: -
Dyn. index: -
Units group: 9_1
Scaling: PERCENT
Max
- [%]
Calculated: -
Dyn. index: -
Units group: 9_1
Scaling: PERCENT
Max
10000.00 [%]
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 2
Func. diagram: 7958
Unit selection: p0595
Expert list: 1
Factory setting
- [%]
Access level: 3
Func. diagram: 7958
Unit selection: p0595
Expert list: 1
Factory setting
200.00 [%]
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130