2 Parameters
2.2 List of parameters
When operating a drive connected to SINUMERIK, which only closes the main contactor with the OFF1 command
(blocksize, chassis), p0867 should be set as a minimum to 50 ms.
p0868

Power unit DC switch debounce time / PU DC sw t_deboun

VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0 [ms]
Description:
Sets the debounce time for the DC circuit breaker for Motor Modules in "chassis" format.
Note:
The following applies if p0868 = 65000 ms:
The debounce time defined internally in the power unit's EEPROM is implemented.
p0869

Sequence control configuration / Seq_ctrl config

VECTOR_G
Can be changed: T
Data type: Unsigned16
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the configuration for the sequence control.
Bit field:
Bit
00
Dependency:
Refer to: p0867
Note:
Re bit 00:
After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869.0 = 1, after withdrawing STO, the switch-on inhibit must be acknowledged via the source of p0840 = 0
(OFF1) – and before the main contactor holding time expires (p0867), should go back to 1, otherwise the main
contactor will open.
r0873

CO/BO: Infeed total operation / INF total oper

B_INF
Can be changed: -
Data type: Unsigned16
P-Group: Commands
Not for motor type: -
Min
-
Description:
Displays the operational readiness of the infeeds when using Smart Line Module (SLM) and Basic Line Module
(BLM) together (mixed operation).
In order that signal BO: r0873 is available at one of the infeeds, then BI: p0874 of the one infeed must be
interconnected to BO: r0863.0 of the other infeed.
Dependency:
Refer to: r0863, p0874
Note:
Mixed operation is not possible with the Active Line Module (ALM)!
264
Signal name
Keep main contactor closed for STO
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
65000 [ms]
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
List Manual (LH2), 04/2014, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
65000 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 bin
0 signal
No
Access level: 2
Func. diagram: 8732, 8832
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150
FP
-