Pn Mac Address Of Station / Pn Mac Of Station; Pn State Cyclic Connections / Pn Stat Cyc Conn; Pn Diagnostics / Pn Diag - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

r8935[0...5]

PN MAC Address of Station / PN MAC of Station

CU_G130_PN,
Can be changed: -
CU_G150_PN
Data type: Unsigned8
P-Group: -
Not for motor type: -
Min
0000 hex
Description:
Displays the MAC address for the onboard PROFINET interface on the Control Unit.
r8936[0...1]

PN state cyclic connections / PN stat cyc conn

CU_G130_PN,
Can be changed: -
CU_G150_PN
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Displays the state of the cyclic PROFINET connections.
For two connections (Shared Device) the display in the index depends on the sequence in which the connections are
established.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
11:
12:
13:
Dependency:
Refer to: p8929
Note:
If value = 10:
If the connection remains in this state, then when using PROFINET IRT the following can apply:
- topology error (incorrect port assignment).
- synchronization missing.
r8937[0...5]

PN diagnostics / PN diag

CU_G130_PN,
Can be changed: -
CU_G150_PN
Data type: Unsigned32
P-Group: -
Not for motor type: -
Min
-
Description:
Display to diagnose the cyclic PROFINET connections.
Index:
[0] = Number of cyclic connections
[1] = Number of send subslots of all connections
[2] = Number of send net data (bytes) of all connections
[3] = Number of receive subslots of all connections
[4] = Number of receive net data (bytes) of all connections
[5] = Connection type (RT, IRT)
Dependency:
Refer to: p8929
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Interrupted
Not connected
Connection starts to be established
Module information expected
Module information received
Module address expected
Module address received
Parameterization data expected
Parameterization data received
Evaluate parameterization data
Connection being established completion expected
Configured controller RUN expected
Configured controller STOP
Configured controller RUN
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
00FF hex
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
13
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
827

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents