Co/Bo: Si Status (Control Unit + Motor Module) / Si Status Cu+Mm; Co/Bo: Si Status (Group Sto) / Si Stat Group Sto; Si Diagnostics / Si Diag - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Re bit 22 and 23:
These bits show via which path the SS1 has been triggered, i.e. what has started the SS1 delay time.
If the SS1 delay time is not started (e.g. because an STO is triggered at the same time), neither of the two bits is set.
r9773.0...31

CO/BO: SI status (Control Unit + Motor Module) / SI status CU+MM

VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the Safety Integrated status on the drive (Control Unit + Motor Module).
Bit field:
Bit
00
01
02
04
05
06
31
Note:
This status is formed from the AND operation of the relevant status of the two monitoring channels.
r9774.0...31

CO/BO: SI status (group STO) / SI stat group STO

VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the status for Safety Integrated of the group to which this drive belongs.
These signals are an AND logic operation of the individual status signals of the drives included in this group.
Bit field:
Bit
00
01
02
04
05
06
31
Dependency:
Refer to: p9620, r9773
Notice:
If a drive belonging to a group is de-activated via p0105, then the signals in r9774 can no longer be correctly
displayed (Remedy: Before de-activating, remove this drive from the group).
Note:
A group is formed by appropriately grouping the terminals for the function "Safe Torque Off" (STO).
The status of a group of n drives is, for drives 1 to n - 1 displayed with a delay of one monitoring clock cycle; this is a
system-related effect.
r9776

SI diagnostics / SI diag

TM54F_MA
Can be changed: -
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
The parameter is used for diagnostics.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Signal name
STO selected in drive
STO active in drive
SS1 delay time active in the drive
SBC requested
SS1 selected in the drive (Basic Functions)
SS1 active in the drive (Basic Functions)
Shutdown paths must be tested
Signal name
STO selected in group
STO active in group
SS1 delay time active in group
SBC requested in group
SS1 selected in group (Basic Functions)
SS1 active in group (Basic Functions)
Shutdown paths of the group must be tested Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 2804
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
Access level: 2
Func. diagram: 2804
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
No
No
No
No
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
FP
2804
2804
2804
2804
-
-
2810
FP
2804
2804
-
2804
-
-
2804
933