Activate/De-Activate Inhibit List / Inh_List Act/Deact; Inhibit Automatic Reference Value Calculation / Inhibit Calc - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0571[0...49]
Inhibit list motor/closed-loop control parameter calculation / Inhib list calc
VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Applications
Not for motor type: -
Min
0
Description:
The inhibit list contains parameters that should be withdrawn from the automatic motor and closed-loop control
parameter calculation (p0340, p0578).
Value:
0:
600:
640:
1082: Maximum speed
1460: Speed controller P gain
1462: Speed controller integral time
1470: Speed controller P gain encoderless
1472: Speed controller integral time encoderless
1520: Torque limit upper/motoring
1521: Torque limit lower/regenerative
1530: Power limit motoring
1531: Power limit regenerative
1590: Flux controller P gain
1592: Flux controller integral time
2141: Speed threshold 1
2142: Hysteresis speed 1
Note:
p0570 defines the number of entries (starting at index 0) for which the inhibit should apply. p0572 can be used to
define for which drive data sets the inhibit list should apply.
If a motor data set is entered into a parameter number, then this is not overwritten as soon as only one drive data set
refers to the motor data set (p0186).
p0572[0...n]

Activate/de-activate inhibit list / Inh_list act/deact

VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Applications
Not for motor type: -
Min
0
Description:
Setting for activating/de-activating the inhibit list.
Depending on the setting, the parameters of the inhibit list (p0571) should be overwritten when calculating the motor
and closed-loop control parameters for the particular drive data set (DDS).
Value:
0:
1:
Note:
If value = 0:
The automatic calculation (p0340, p0578) also overwrites the parameters of the inhibit list (p0571).
If value = 1:
The automatic calculation (p0340, p0578) does not overwrite the parameters of the inhibit list (p0571).
p0573

Inhibit automatic reference value calculation / Inhibit calc

B_INF, VECTOR_G
Can be changed: U, T
Data type: Integer16
P-Group: Applications
Not for motor type: -
Min
0
Description:
Setting to inhibit the calculation of reference parameters (e.g. p2000) when automatically calculating the motor and
closed-loop control parameters (p0340, p3900).
214
No parameter
Motor temperature sensor
Current limit
No
Yes
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2142
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
1
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150