Co: Speed Limit Positive Effective / N_Limit Pos Eff; Ci: Speed Limit In Positive Direction Of Rotation / N_Limit Pos; Co: Speed Limit In Negative Direction Of Rotation / N_Limit Neg; Co: Speed Limit Negative Effective / N_Limit Neg Eff - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

r1084

CO: Speed limit positive effective / n_limit pos eff

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Display and connector output for the active positive speed limit.
Dependency:
Refer to: p1082, p1083, p1085
p1085[0...n]

CI: Speed limit in positive direction of rotation / n_limit pos

VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for the speed limit of the positive direction.
p1086[0...n]

CO: Speed limit in negative direction of rotation / n_limit neg

VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-210000.000 [rpm]
Description:
Sets the speed limit for the negative direction.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
r1087

CO: Speed limit negative effective / n_limit neg eff

VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
- [rpm]
Description:
Display and connector output for the active negative speed limit.
Dependency:
Refer to: p1082, p1086, p1088
p1088[0...n]
CI: Speed limit in negative direction of rotation / n_limit neg
VECTOR_G
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Setpoints
Not for motor type: -
Min
-
Description:
Sets the signal source for the speed/velocity limit of the negative direction.
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: p2000
Max
-
Calculated: -
Dyn. index: DDS, p0180
Units group: 3_1
Scaling: p2000
Max
0.000 [rpm]
Calculated: -
Dyn. index: -
Units group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: CDS, p0170
Units group: -
Scaling: p2000
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 3050, 3095
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 3
Func. diagram: 3050
Unit selection: -
Expert list: 1
Factory setting
1083[0]
Access level: 2
Func. diagram: 3050
Unit selection: p0505
Expert list: 1
Factory setting
-40000.000 [rpm]
Access level: 3
Func. diagram: 3050, 3095
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 3
Func. diagram: 3050
Unit selection: -
Expert list: 1
Factory setting
1086[0]
299

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents