Number Of Command Data Sets (Cds) / Cds Count; Number Of Drive Data Sets (Dds) / Dds Count; Motor Data Sets (Mds) Number / Mds Number; Encoder 1 Encoder Data Set Number / Enc 1 Eds Number - Siemens SINAMICS G150 Manual

Drive converter chassis
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0170

Number of Command Data Sets (CDS) / CDS count

B_INF
Can be changed: C1(3)
Data type: Unsigned8
P-Group: Commands
Not for motor type: -
Min
1
Description:
Sets the number of Command Data Sets (CDS).
Note:
It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
p0170
Number of Command Data Sets (CDS) / CDS count
VECTOR_G
Can be changed: C1(3)
Data type: Unsigned8
P-Group: Commands
Not for motor type: -
Min
2
Description:
Sets the number of Command Data Sets (CDS).
Note:
It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
p0180

Number of Drive Data Sets (DDS) / DDS count

VECTOR_G
Can be changed: C1(3)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
1
Description:
Sets the number of Drive Data Sets (DDS).
p0186[0...n]

Motor Data Sets (MDS) number / MDS number

VECTOR_G
Can be changed: C1(4)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
0
Description:
Using the parameter, each Drive Data Set (= index) is assigned the associated Motor Data Set (MDS).
The parameter value therefore corresponds to the number of the assigned motor data set.
p0187[0...n]

Encoder 1 encoder data set number / Enc 1 EDS number

VECTOR_G
Can be changed: C1(4)
Data type: Unsigned8
P-Group: Data sets
Not for motor type: -
Min
0
Description:
Assign a drive data set (= index) the corresponding encoder data set (EDS) for encoder 1.
The value corresponds to the number of the assigned encoder data set.
Example:
Encoder data set 0 should be assigned to encoder 1 in drive data set 2.
--> p0187[2] = 0
96
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
2
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
4
Calculated: -
Dyn. index: -
Units group: -
Scaling: -
Max
32
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
15
Calculated: -
Dyn. index: DDS, p0180
Units group: -
Scaling: -
Max
99
List Manual (LH2), 04/2014, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
2
Access level: 2
Func. diagram: 8565
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 3
Func. diagram: 8575
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 4700, 8570
Unit selection: -
Expert list: 1
Factory setting
99
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g130

Table of Contents